FVP 110 Fieldbus Valve Positioner Manual
202
GE Energy
8 6008 6108 OUT_D — Man Indicates the output value and its status.
9 6009 6109 SIMULATE_D disable — Used to determine whether to use the limit
switch signal input from the transducer block or
use the user-set value. When this parameter is
set to disable, the block uses the actual input
value and status.
10 6010 6110 XD_STATE 0 Index to the text describing the states of the
discrete value obtained from the transducer,
but not supported by FVP110
11 60011 6111 OUT_STATE 0 Index to the text describing the states of a
discrete output, but not supported by FVP110.
12 6012 6112 GRANT_
DENY
0 Used to check whether various user operations
can be put into effective. Before operations, in
the GRANT parameter component, set the bits
(to 1) corresponding to the intended
operations. After the operations, check the
DENY parameter component. If the
corresponding bits are not set (to 1) in DENY, it
proves that the corresponding operation has
been put into effective.
13 6013 6113 IO_OPTS 0 O/S Settings for the I/O processing of the block.
14 6014 6114 STATUS_
OPTS
0 O/S Defines block actions depending on block
status conditions.
15 6015 6115 CHANNEL 2 or 3 O/S Defines the channel number of the hardware
channel connected to the transducer block.
Always set 2 for the DI1 block and 3 for DI2 in a
FVP110.
16 6016 6116 PV_FTIME – — Time constant of filter for PV_D.
17 6017 6117 FIELD_VAL_
D
– Status of limit switch signal obtained from the
transducer block
18 6018 6118 UPDATE_EV
T
– – Shows the contents of an update event upon
occurrence.
19 6019 6119 BLOCK_ALM – – Shows the contents of a block alarm upon
occurrence.
20 6020 6120 ALARM_SUM enable Shows the alarm summary (current alarm
statuses, acknowledged/unacknowledged
states, masking states) for the DI block.
Table 63 DI Block Parameters (Continued)
Relative
Index
Index Parameter
Name
Default
(factory
setting)
Write Description
DI1 DI2