FVP 110 Fieldbus Valve Positioner Manual
214
GE Energy
29 17529 ARITH_TYPE 0 The identification number of the arithmetic
algorithm. 1 to 9.
30 17530 BAL_TIME 0 This specifies the time for the internal working
value of bias or ratio to return to the operator
set bias or ratio, in seconds.
31 17531 BIAS The bias value used in computing the function
block output, expressed in engineering units.
OUT_SCALE +/- 10%.
32 17532 GAIN 0 Dimensionless value used by the block
algorithm in calculating the block output.
33 17533 OUT_HI_LIM 100% Limits the maximum output value.
OUT_SCALE +/- 10%.
34 17534 OUT_LO_LIM 0% Limits the minimum output value. OUT_SCALE
+/- 10%.
35 17535 UPDATE_EV
T
Read only
An alert for any change in the static data.
This alert can notify interface devices that
keep track of changes that one or more
changes have occurred. The relative
parameter index and its associated block
index is included in the alert, along with the
new value of ST_REV
36 17536 BLOCK_ALM Shows the contents of an alarm event upon
occurrence.
Table 67 AR (Arithmetic) Block Parameters (Continued)
Relative
Index
Index Parameter
Name
Default
(factory
setting)
Write Description