FVP 110 Fieldbus Valve Positioner Manual
12
GE Energy
❑ Non-incendive for Class I, Division 2, Groups A, B, C, D and Class I, Zone 2,
Group IIC
❑ Indoor/Outdoor hazardous locations, NEMA 4X Ambient Temperature: -40 to 60 °C
Note 2. Electrical Data
Rating l
For Groups A, B, C, D, E, F and G or Group IIC:
❑ Maximum Input Voltage Vmax: 24 V
❑ Maximum Input Current Imax: 250 mA
❑ Maximum Input Power Pmax: 1.2 W
❑ Maximum Internal Capacitance Ci: 1.76 nF
❑ Maximum Internal Inductance Li: 0 µH
or
Rating 2
For Groups A, B, C, D, E, F and G or Group IIC:
❑ Maximum Input Voltage Vmax: 17.5 V
❑ Maximum Input Current Imax: 360 mA
❑ Maximum Input Power Pmax: 2.52 W
❑ Maximum Internal Capacitance Ci: 1.76 nF
❑ Maximum Internal Inductance Li: 0 μH
or
Rating 3
For groups C, D, E, F and G or Group IIB:
❑ Maximum Input Voltage Vmax: 17.5 V
❑ Maximum Input Current Imax: 380 mA
❑ Maximum Input Power Pmax: 5.32 W
❑ Maximum Internal Capacitance Ci: 1.76 nF
❑ Maximum Internal Inductance Li: 0 μH
❑ In the rating 1, the output current of the barrier must be limited by a resistor Ra
such that Io = Uo/Ra.
❑ In the rating 2 or 3, the output characteristics of the barrier must be the type of
trapezoid which are certified as the FISCO model.