EasyManua.ls Logo

GE FVP110 - Block setting

GE FVP110
292 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
FVP 110 Fieldbus Valve Positioner Manual
80
GE Energy
CENELEC ATEX (KEMA) Flameproof Approval*2
Applicable standard: EN50014, EN50018
Certificate: KEMA 02ATEX2159
II 2G EEx d IIC T6 and T5 Amb. Temp.: –40 to 75 °C (–40 to 167 °F) for T6, –40 to 80 °C (–40 to
176 °F) for T5
KF2
CENELEC ATEX (KEMA) Intrinsically Safe Approval*2
Applicable standard: EN50014, EN50020, EN500284, EN50281-1-1
Certificate: KEMA 02ATEX1274X
1G/1GD EEx ia IIC T4:
Ui=17.5 V, Ii=360 mA, Pi=2.52 W, Ci=1.76 nF, Li=0 H (FISCO model)
Ui=24.0 V, Ii=250 mA, Pi=1.2 W, Ci=1.76 nF, Li=0 H (Entity model)
1G/1GD EEx ia IIB T4:
Ui=17.5 V, Ii=380 mA, Pi=5.32 W, Ci=1.76 nF, Li=0 H (FISCO model)
1D Um=32.0 V:
Tamb(1G): –40 to 60 °C (–40 to 140 °F), Tamb(1D): –40 to 80 °C (–40 to 176 °F),
Tamb(1GD): –40 to 60 °C (–40 to 140 °F), T100 °C (1D, 1GD)
Enclosure: IP65
KS25
CENELEC ATEX Type n declaration*2 *5
Applicable standard: EN60079-15
EEx nL IIC T4 Amb. Temp. : –40 to 60 °C (–40 to 140 °F), Enclosure: IP65
Ui=32 V, Ci=1.76 nF, Li=0 H
KN25
TIIS Flameproof Approval*3
Certificate: TC15453, TC15452 for option code /BP
Ex d IIC T6 Amb. Temp.: –20 to 60 °C
JF3
*1: Applicable for Connections code 3.
*2: Applicable for Connections code 3 and 6.
*3: Applicable for Connections code 1, 3 and 6.
*4: If cable wiring is to be used to a TIIS flameproof type transmitter, do not fail to add the GE Masoneilan
assured flameproof packing adapter.
*5: Applicable for Option code EE.
Table 11 Optional Specifications For Explosion Protected Types (Continued)
Description Code

Table of Contents

Related product manuals