EasyManua.ls Logo

GE Multilin D400 - Example System Configuration

GE Multilin D400
192 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CHAPTER 10: INTRODUCING THE D400 CONFIGURATION
D400 SUBSTATION GATEWAY INSTRUCTION MANUAL GE INFORMATION 125
Example System Configuration
Figure _ shows an example system configuration.
Figure 58: Sample system configuration
NOTE
†This field is configured in minutes, so the value entered in the configuration tool would be
-420 and -300 respectively. However, hours are shown in the diagram above for clarity.
Remote access
via web-based HMI
Local access to
command line via
RS232 port
Even though the
D400 device is located
in the local time zone of UTC -7, the
D400
system clock is set to UTC time.
Local device with
clock set to UTC -7
Remote client with clock
set to UTC -5
PC clock is set to
local time zone (
-8)
No configuration
necessary
d400cfg System Clock: UTC time
d400cfg Time Zone: -7
DNP Client Map File
Time Offset: -7
DNP Server Application
Parameters
Time Offset: -5
If an event occurs at 13:00 UTC…
Event timestamp is
displayed as
05:00
Event timestamp is
displayed as
06:00
The D400 system database records the
event timestamp as
13:00
Local device reports
the event at
06:00
Remote client receives the
event timestamp as
08:00

Table of Contents

Related product manuals