Before you remove the battery…
Note the following items before you begin battery replacement:
• Disconnect power to the D400 before changing the battery.
• Avoid exposure to high temperatures, such as soldering or spot-welding
• Avoid excessive force to terminals
• Use extreme caution and proper procedures for servicing electrostatically sensitive
components. Electrostatically sensitive components are located near the battery.
Removing the battery causes the internal clock to reset and the non-volatile RAM to be
erased.
Supported battery types
The D400 is supplied with a 1/2AA 3.6 V 0.9 Ah Lithium Thionyl Chloride non-rechargeable
battery (GE Item No. 980-0038). The following battery types may be used as a replacement.
Table 51: Supported Battery Types
To insert or replace the D400 battery
Ensure that all hazardous live circuits are isolated or disconnected before attempting
battery replacement.
1. Power down the D400.
2. Remove the D400 main module from the chassis. See “Removing the D400 main
module” on page 159.
3. Using a plastic or other non-conductive tool, pry the black plastic clip holding the
battery cover away from the battery holder BT1. When free, the battery and clip can
be removed together.
4. Remove the cover from the battery holder and keep it.
5. Place the new battery into the battery holder, ensuring polarity is correct.
6. Replace the cover and press down until the clips click into the retaining notches of the
battery holder.
7. Replace the D400 main module.
8. Power up the D400 and verify that the Power LED is illuminated.
Manufacturer Manufacturer part number.
Tadiran
®
TL-2150
Tadiran TL-4902
Tadiran TL-5101
Tadiran TL-5902
Toshiba
®
ER3V
Toshiba ER4V
Saft
®
LS-14250
Saft LS-14250C
Sonnenschein
®
SL-350
Sonnenschein SL-750
Maxell
®
ER3
XENO Energy XL-050F