EasyManuals Logo

GE Multilin D400 User Manual

GE Multilin D400
192 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #157 background imageLoading...
Page #157 background image
CHAPTER 12: USING THE D400 LOCAL CONFIGURATION UTILITY
D400 SUBSTATION GATEWAY INSTRUCTION MANUAL GE INFORMATION 157
Figure 61: ARRM connections
Suppress forced qualities to masters
From the Suppress forced qualities to masters menu, you can suppress forced
qualities being reported to the IEC101-104 Master for a configured duration of time.
When a master is configured in this mode:
All of the values with Forced/Substituted flags are communicated to the Master as
value changes only.
All other flags are still communicated normally.
Only elevated users (that is, administrator users with root access privileges) can execute
this functionality.
Re-starting the processes has no impact on the functionality.
This functionality is cancelled (and the forced qualities are reported back to the master):
Upon time expiration, or
When the D400 is rebooted.
Restore factory default
A root user or a super (“sudo”) user can restore a D400 to the factory default (or “clean”)
configuration.
After this command is initiated (prior to restoration), you are prompted to make a backup
copy of the current configuration onto a USB key.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Multilin D400 and is the answer not in the manual?

GE Multilin D400 Specifications

General IconGeneral
BrandGE
ModelMultilin D400
CategoryGateway
LanguageEnglish

Related product manuals