116 ADV100 • Functions description and parameters list
COMMANDS menu.
0 Ignore
1 Warning
2 Disable
3 Stop
4 Fast stop
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.14 4544 Overspeedholdoff ms UINT16 0 0 5000 RW FVS
Setting of the delay between the signalling of the motor overspeed alarm Overspeed and enabling of the alarm. If
an alarm condition occurs, the drive will wait for the set time before enabling the alarm. If the alarm is removed within
the set time, the drive will not indicate any alarm condition.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.15 4550 SpdRefLossthreshold rpm INT16 100 0 CALCI RW FVS
Setting of the threshold below which the speed reference loss alarm SpdRefLoss occurs.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.16 4552 SpdRefLossactivity ENUM Warning 0 4 RW FVS
Setting of the behaviour of the drive in case of a speed reference loss alarm SpdRefLoss. This alarm indicates that
the difference between the speed regulator reference and the actual motor speed is more than 100 rpm.
This alarm must be disabled (= 0 Ignore) when parameter 556Controlmode is set to Torque (0) or when parameter
2354 is set to a value other than zero.
0 Ignore
1 Warning
2 Disable
3 Stop
4 Fast stop
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.17 4554 SpdRefLossholdoff ms UINT16 1000 0 10000 RW FV_
Setting of the delay between the signalling of the speed reference loss alarm condition SpdRefLoss and enabling of
the alarm. If an alarm condition occurs, the drive will wait for the set time before enabling the alarm. If the alarm is
removed within the set time, the drive will not indicate any alarm condition.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.18 4560 SpdFbkLossactivity ENUM Disable 0 4 RW FV_
Setting of the behaviour of the drive in case of a speed feedback loss alarm SpdFbkLoss. This alarm indicates the
loss of the encoder feedback signals.
0 Ignore
1 Warning
2 Disable
3 Stop
4 Fast stop
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.19 4562 SpdFbkLossholdoff ms UINT16 200 0 10000 RW FVS
Setting of the delay between the signalling of the speed feedback loss alarm condition SpdFbkLoss and the ena-
bling of the alarm. If an alarm condition occurs, the drive will wait for the set time before enabling the alarm. If the
alarm is removed within the set time, the drive will not indicate any alarm condition.