ADV100 Functions description and parameters list 117
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.20 4564 SpdFbkLossthreshold rpm INT16 100 5 CALCI RW FVS
For SE (single ended) encoders and with parameters 2110 or 5110 = (3) Control A-B-SE.
The Speedfbkloss[22] alarm control is enabled when the speed reference is higher than the value set in this
parameter
If using incremental digital encoders in single-ended mode, this parameter sets the limit above which the drive ex-
ecutes the action set with parameter 4560 SpdFbkLossactivity.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.21 4570 Driveovldactivity ENUM Ignore 0 4 ERW FVS
Setting of the behaviour of the drive in case of a drive overload alarm Driveovld. This alarm indicates that the drive
overload threshold has been reached.
0 Ignore
1 Warning
2 Disable
3 Stop
4 Fast stop
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.22 4572 Motorovldactivity ENUM Warning 0 4 ERW FVS
Setting of the behaviour of the drive in case of a motor overload alarm Motorovld[14]. This alarm indicates that the
motor overload threshold has been reached.
0 Ignore
1 Warning
2 Disable
3 Stop
4 Fast stop
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.23 4574 Bresovldactivity ENUM Disable 0 4 ERW FVS
Setting of the behaviour of the drive in case of a braking resistor overload alarm Bresovld. This alarm indicates that
the braking resistor overload threshold has been reached.
0 Ignore
1 Warning
2 Disable
3 Stop
4 Fast stop
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.24 4582 HTsensrestart ENUM Disable 0 1 ERW FVS
Enabling of automatic restart after the drive heatsink overtemperature alarm HeatsinkSOTUT[10].
0 Disable
1 Enable
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.25 4584 HTsensrestarttime ms UINT16 20000 120 60000 ERW FVS
Setting of the time within which the HeatsinkSOTUT[10]alarm must be reset in order to perform automatic restart.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.26 4600 InAiractivity ENUM Stop 0 4 ERW FVS
Setting of the behaviour of the drive in case of an intake air overtemperature alarmIntakeairOT[11].This alarm
indicates that the temperature of the intake cooling air is too high.

Table of Contents

Other manuals for gefran SIEIDrive ADV100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the gefran SIEIDrive ADV100 and is the answer not in the manual?

gefran SIEIDrive ADV100 Specifications

General IconGeneral
Brandgefran
ModelSIEIDrive ADV100
CategoryController
LanguageEnglish

Related product manuals