118 ADV100 • Functions description and parameters list
0 Ignore
1 Warning
2 Disable
3 Stop
4 Fast stop
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.27 4602 InAirrestart ENUM Disable 0 1 ERW FVS
Enabling of automatic restart after the intake air overtemperature alarm IntakeairOT[11].
0 Disable
1 Enable
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.28 4604 InAirrestarttime ms UINT16 1000 120 30000 ERW FVS
Setting of the time within which the IntakeairOT[11]alarm must be reset in order to perform automatic restart.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.29 4606 InAirholdoff ms UINT16 10000 0 30000 ERW FVS
Setting of the delay between the signalling of the intake air overtemperature alarm IntakeairOT[11] and enabling
of the alarm. If an alarm condition occurs, the drive will wait for the set time before enabling the alarm. If the alarm is
removed within the set time, the drive will not indicate any alarm condition.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.30 4610 Desatrestart ENUM Disable 0 1 ERW FVS
Enabling of automatic restart after the desaturation alarm Desat. This alarm indicates a short circuit between the mo-
tor phases or on the power bridge.
0 Disable
1 Enable
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.31 4612 Desatrestarttime ms UINT16 2000 1000 10000 ERW FVS
Setting of the time within which the Desaturation alarm must be reset in order to perform automatic restart. (Time
with alarm signal active + 1000 msec).
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.32 4620 IOverCrestart ENUM Disable 0 1 ERW FVS
Enabling of automatic restart after the drive overcurrent alarm. This alarm indicates an overcurrent (or short circuit
between phases or towards the ground).
0 Disable
1 Enable
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.33 4622 IOverCrestarttime ms UINT16 2000 1000 10000 ERW FVS
Setting of the time within which the Overcurrent alarm must be reset in order to perform automatic restart. (Time
with alarm signal active + 1000 msec).
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.34 4630 OverVrestart ENUM Disable 0 1 ERW FVS
Enabling of automatic restart after the overvoltage alarm. This alarm indicates an overvoltage on the intermediate
circuit (DC link)