ADV100 • Functions description and parameters list 119
0 Disable
1 Enable
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.35 4632 OverVrestarttime ms UINT16 2000 1000 10000 ERW FVS
Setting of the time within which the Overvoltage alarm must be reset in order to perform automatic restart. (Time
with alarm signal active + 1000 msec).
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.36 4640 UnderVrestart ENUM Enable 0 1 ERW FVS
Enabling of automatic restart after the undervoltage alarm. This alarm indicates an undervoltage on the intermediate
circuit (DC link)
0 Disable
1 Enable
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.37 4642 UnderVrestarttime ms UINT16 1000 120 10000 ERW FVS
Setting of the time within which the Undervoltage alarm must be reset in order to perform automatic restart. (Time
with alarm signal active + 100 msec).
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.38 4650 UVRepattempts UINT16 5 0 1000 ERW FVS
Setting of the maximum number of attempts at automatic restart after the Undervoltage alarm before a MultUnder-
voltage alarm is generated. If this parameter is set to 1000 an innite number of attempts are available.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.39 4652 UVRepdelay s UINT16 240 0 300 ERW FVS
Setting of the time within which, if no automatic restarts are executed after the Undervoltage alarm, the attempts
counter is reset. In this way the number of attempts set in UVRepattempt are still available.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.40 4660 PhLossactivity ENUM Disable 0 4 ERW FVS
Setting of the behaviour of the drive in case of a no phase alarm. This alarm indicates the absence of a drive power
supply phase.
0 Ignore
1 Warning
2 Disable
3 Stop
4 Fast stop
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.41 4662 PhLossrestart ENUM Disable 0 1 ERW FVS
Enabling of automatic restart after the no phase alarm.
0 Disable
1 Enable
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.42 4664 PhLossrestarttime ms UINT16 1000 120 10000 ERW FVS
Setting of the time within which the Phaselossalarm must be reset in order to perform automatic restart. (Time with
alarm signal active + 100 msec).