ADV100 • Functions description and parameters list 121
34 Plc2 fault
35 Plc3 fault
36 Plc4 fault
37 Plc5 fault
38 Plc6 fault
39 Plc7 fault
40 Plc8 fault
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.49 4720 Almautoresettime s FLOAT 0 0 60.0 ERW FVS
Setting of the time interval that must pass before executing an automatic reset.
If no alarms are enabled the drive is set to restart.
If some alarms are still enabled the drive is set to execute a new attempt at automatic reset.
At each attempted reset a counter increases. If the limit set in the Alm autoreset number parameter is reached the
drive is set to make no more attempts at reset and waits for a user reset.
The counter is set to zero when an automatic reset or user reset is performed and no alarms are enabled.
If the parameter is 0 the function is disabled.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.50 4722 Almautoresetnumber UINT16 20 0 100 ERW FVS
Setting of the maximum number of attempted automatic resets.