ADV100 Troubleshooting 151
Index Errormessage
shownonthe
display
Sub-code Description
13 Plc1
Reserved messages and dedicated to the PLC application. See the application manual.
14 Plc2
15 Plc3
16 Plc4
17 Optionbusfault
Condition: this may occur when the drive is turned on, during fieldbus card setup. Error during configuration or communication error.
XXX0H-X If the first digit to the left of “H” in the alarm sub-code is 0, the error regards a communication problem.
XXX0H-X If the first digit to the left of “H” in the alarm sub-code is other than 0, the error regards a configuration problem.
Solution: For configuration errors, check the configuration of the bus communication, type of bus, baudrate, address, parameter setting.
For communication errors, check wiring, termination resistors, disturbance immunity, timeout settings.
For further details, please refer to the user guide for the specific bus.
18 Keyfailed
Condition: this may occur when powering the drive, if the incorrect enable key is inserted for a given firmware function.
0001H-1 Incorrect PLC key. PLC application not available.
Solution: Ask Gefran to supply the correct key to enable the desired firmware function.
19 Keyexpiring
Condition:this may occur at drive power-on if the incorrect enabling key was inserted for a given firmware function. At this stage the
firmware function can still be used freely, but this time limit is about to expire.
xxxxH-x Number of hours for which the function can still be used freely.
Solution: Ask Gefran for the correct key to enable the desired firmware function.
20 Paramerror
Condition: if an error occurs during activation of the parameter database saved in flash; the alarm is inserted in the alarm list and alarm
log.
XXX0H-X The code XXXXH-X indicates the IPA of the parameter that has been set outside the range allowed when the database is
enabled.
Solution: Set the parameter causing the error to a value within the range and run Saveparameters. Switch the drive off and then switch
it back on again.
If the IPA of the parameter is not shown in the manual, contact the service centre.
21 Encodererror
Condition:this condition may occur when the drive is powered during encoder setup each time parameter552Regulationmodeis set.
100H-
2564
Cause: An error occurred during setup; the information received from the encoder is not reliable. If the encoder is used for
feedback the Speedfbkloss [22] alarm is also generated.
Solution:Take the recommended action for the Speedfbkloss[22] alarm.
200H-512 Cause: The firmware on the optional encoder card is incompatible with that on the regulation card. The information received
from the encoder is not reliable
Solution: Contact Gefran in order to update the firmware on the optional encoder card.
22
Optionscfg
changed
Condition: this may occur when powering the drive if an expansion card has been removed or replaced or the incorrect enable key is
inserted for a given firmware function.
0064H-
100
Card removed from slot 1
0014H-20 Card removed from slot 2
0003H-3
0078H-
120
Card removed from slot 1 and from slot 2
0067H-
103
0017H-23
007BH-
123
Solution: Check the hardware configuration, then press ESC. Save the parameters (Saveparameters, menu 04.01 par 550) to save the
new hardware configuration.
Note! For any messages that are displayed but not included in this list reference should be made to the manual for the applica-
tion used by the drive.