ADV100 • Functions description and parameters list 81
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
21.19 2474 Dampingthreshold2 Hz INT16 30 5 100 ERW V
Setting of the second damping gain regulation threshold. These settings are usually effective for intermediate fre-
quencies and make it possible to limit motor oscillations.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
21.20 2480 Vfminfrequency Hz FLOAT 1.0 0.2 5.0 ERW V
Setting of the minimum frequency in the V/f control mode. This represents the minimum output frequency, below
which frequency regulations are ineffective. It is not possible to go below this value, regardless of the reference that
has been set.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
21.21 2482 Vfminfreqdelay ms UINT16 800 0 5000 ERW V
Setting of the delay for the minimum frequency signal in the V/f control mode.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
21.22 2490 DigVfscale FLOAT 16/32 1.0 0.0 1.0 ERWZ V
Setting of a digital multiplier factor for the drive output voltage in the V/f mode.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
21.23 2492 Vfscalesrc LINK 16/32 3374 0 16384 ERW V
Selection of the origin (source) of the signal to be used to set a multiplier factor for the drive output voltage. The as-
sociable functions are listed in the “L_REF” selection list.