AC GENERATORS
PART 2
Page 29
Section 2.3
Troubleshooting Flow Charts
STOP TESTS
VOLTAGE AND
FREQUENCY O.K.
STOP TESTS
Problem 3 – Generator Produces High Voltage at No-Load
HIGH LOW
FREQUENCY O.K.,
BUT VOLTAGE HIGH
FREQUENCY O.K.,
BUT VOLTAGE IS
STILL HIGH
REPLACE DEFECTIVE
VOLTAGE REGULATOR
TEST 11 – CHECK
AC OUTPUT
VOLTAGE
TEST 14 – ADJUST
VOLTAGE
REGULATOR
TEST 12 – CHECK
AC OUTPUT
FREQUENCY
FREQUENCY AND
VOLTAGE O.K.
FREQUENCY O.K.,
BUT VOLTAGE
HIGH
TEST 13 – ADJUST
ENGINE
GOVERNOR
DISCONTINUE
TESTING
TEST 13 – CHECK
AND ADJUST ENGINE
GOVERNOR
TEST 16 – CHECK
VOLTAGE AND
FREQUENCY
UNDER LOAD
TEST 15 – CHECK
FOR OVERLAOD
CONDITION
GO TO “PROBLEM 23 –
ENGINE STARTS HARD AND
RUNS ROUGH/LACKS POWER”
BOTH
LOW
NOT OVERLOADED
GOOD GOOD
BAD
GOOD
ENGINE CONDITION GOOD
REPAIR OR REPLACE
LOOK FOR A SHORTED
CONDITION IN A
CONNECTED LOAD OR IN
ONE OF THE LOAD CIRCUITS
REDUCE LOADS TO
UNIT’S RATED
CAPACITY
OVERLOADED
Problem 4 - Voltage and Frequency Drop Excessively When Loads Are Applied
TEST 9 – CHECK
STATOR AC
POWER WINDINGS

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Generac Power Systems CorePower and is the answer not in the manual?

Generac Power Systems CorePower Specifications

General IconGeneral
BrandGenerac Power Systems
ModelCorePower
CategoryPortable Generator
LanguageEnglish

Related product manuals