GM Energy V2H Bundle Installation Manual 86
Commissioning App Busbar
Settings
Input
CT location
CT at MID (partial load monitoring)
Export Limit Current
Perform the following calculation for this input:
1.2 x Busbar Capacity Main Breaker Rating AC Solar Rating
(Default can be set to 0 A for V2H Installs)
No external metering possible
If a meter is not possible to be placed at the grid or at the MID, the installer can calculate and input a single source output limit
for the Inverter.
Commissioning App Busbar Setting
Input
CT location
Single source output
Inverter Limit Current
0 - 48 A
Default can be set to 0 A