131
7-06 Delivery system
Feeding system
advance time
( 5) 5s
• Feeding system
Time during which the feeding system runs before the
fuel metering.
7-08 Delivery system
Feeding system
Lag time for burnout
( 60) 60s
• Feed system lag time
When switching to the “burn out” phase.
(1 - 90 s)
7-09 Delivery system
Feeding system
Minimum pause
( 5) 5s
• Feeding system
If the calculated pause contingent on the combustion
control lies below the set value, the feeding system runs
without pausing. (only for the setting Par. 7-02 cyc-
les)
7-10 Delivery system
Dosage
shortest runtime
( 3) 3s
• Shortest running time of the dosage system
How long the impulse should minimally be.
(0 - 60 s)
7-11 Delivery system
Dosage
shortest pause
( 3) 3s
• Shortest pause time of dosage system
How long the pause time should minimally be.
(0 - 60 s)
7-12 Delivery system
Dosage
reverse current
( 3.0) 3.0A
• Dosage
After exceeding the set motor current, the motor reverses
up to three times. Then a fault message is issued. (0.1 -
10.0 A)
7-14 Delivery system
Dosage
reverse runtime
( 1) 1s
• Dosage
Reverse running time when the set reverse current is
exceeded.
(0 - 3 s)
7-16 Delivery system
Continuous running
Cycles
• Delivery system
Option to set continuous running or cycles.
7-17 Delivery system
Delivery system
runtime
( 3) 3s
• Delivery system
Set the delivery system runtime (only for the setting
Par. 7-16 cycles)
7-18 Delivery system
Delivery system
Pause time
( 3) 3s
• Delivery system
Set the delivery system pause time (only for the setting
Par. 7-16 cycles)
No. Display Description
Table 6/9 - System level / 7 - Delivery system