Diagnostics
Diagnostics allow trending and display of LON specific parameters such as:
• Transmission erros
• Lost messages
• Collisions
• Etc.
For trending LON parameters, basic settings such as start and stop time, trend
buffer values and enable/disable logging are defined.
Diagnostics also allow BACnet diagnostic by showing the actual communication
status on the BACnet bus and search for BACnet objects and identifiers.
EMAIL ALARMING
Purpose Sending an email to a definable email-recipient in case of alarms of selectable
datapoints. Alarms may be generated for each datapoint that has the appropriate
notification class assigned and the alarm reporting enabled. The email includes an
attachment (.TXT) that shows a detailed description of the alarm data, for example:
Democase_Controller
http://192.168.200.10
URGENT (193)
Outdoor_Temperature
2008-March-12 We 14:29:16
Notify Type: Alarm
Event Type: Out Of Range
Description: Smart_IO_AI2
Present Value: 50 °C
Low Limit: 3 °C - High Limit: 40 °C
Steps Setting up the email alarming process includes the following major steps:
In CARE
• Enable Excel Web 2.0 Application format for the controller
• Enter E-Mail alarming properties
• Connect to controller
• Translate and download application
• Download controller settings
For information on the procedure, please refer to the CARE User Guide,
EN2B-0182GE51.
In the Excel Web HTML Interface
1. Assign email address to the user that receives the alarm email(s)
(recipient)
• Assign email address (recipient) to the notification class
• Define alarming conditions for datapoint(s) that should send alarm
emails
• Send Test Email
NOTE: Steps 1 through 3 can also be done in CARE
For detailed information on the procedure, pleaser refer to “Email Alarming” in the
“Operating the Excel Web HTML Interface” section.