USER GUIDE FALCON
65 EN2Z-0962GE51 R0715
-
Relinquish Default 20,0 °C
The priority list can include max. 16 values and will be continuously updated by
written values caused by the command-issuing entities.
The value of the highest priority level is always written to the present value as long
as the priority list is not empty. If the list is empty, the user-definable relinquish
default value is written to the present value.
For the example in the table, Critical Equipment Control has the highest priority and
is written to the present value. As soon as the priorities 5 and 8 are relinquished e.g.
via BACnet service, the relinquish default of 20,0°C will be valid for the present
value.
Polarity
Datapoint Type AI AO AV BI BO
BV MI MO
MV
PC RI RO
HTML Interface CARE
Editing - x
The polarity indicates the relationship between the physical state of the input and
the logical state represented by the present value. If the polarity is NORMAL, then
the ACTIVE state of the present value is also the ACTIVE or ON state of the
physical input. If the polarity is REVERSE, then the ACTIVE state of the present
value is the INACTIVE or OFF state of the physical Input.
NORMAL INACTIVE OFF or INACTIVE not running
NORMAL ACTIVE ON or ACTIVE running
REVERSE INACTIVE ON or ACTIVE not running
REVERSE ACTIVE OFF or INACTIVE running
Property
AI AO AV BI BO
BV MI MO
MV
PC RI RO
User Interface HTML Interface CARE
-
Equivalent
By default, the present value is selected as property of a reference input point in
CARE.
Read Access Level
AI AO AV BI BO
BV MI MO
MV
PC RI RO
User Interface HTML Interface CARE
- x
Equivalent