FALCON USER GUIDE
EN2Z-0962GE51 R0715 192
(Applies to AO, AV, BO, BV, MO, and MV datapoint types only)
1. In the Details dialog box of the selected datapoint, select the Command
Priorities tab.
Here you can view the command priority levels and enter/change the relinquish
default value.
The priority list has descending priority. The value on the highest priority level is
written to the present value.
Relinquish Default
This value will be written to present value, if all values in the priority list are
invalid.
Enter relinquish default value into the field.
3. To save changes, click the SUBMIT button.
For detailed description, please refer to the "Relinquish Default" and "Priority Level"
sections.
View / Edit Event Enrollment Alarming
Event enrollment alarming can be used for observing the following datapoint
properties:
Present value
Acknowledged transitions (datapoint alarms)
Status flag conditions
Elapsed active time / count limits