USER GUIDE FALCON
53 EN2Z-0962GE51 R0715
Low limit plus deadband and high limit minus deadband
Fig. 13. Deadband (1) of analog datapoints
Description
Datapoint Type AI AO AV BI BO BV MI MO
MV PC RI RO
User Interface
HTML Interface CARE
Editing - X
Equivalent
Descriptor
Shows the descriptive Text, which has been entered as Descriptor for the datapoint
in CARE.
A controller contains up to 600 physical datapoints and an unlimited number of value
datapoints. When creating datapoints, an individual datapoint name is assigned to
each of these datapoints.
Plain-language descriptors can be created with an unlimited number of characters
each. These descriptors are then assigned to datapoints via the property
"Descriptor".
Descriptors complete the information concealed behind the datapoint name. They
can contain, for instance, a reference to a section of a building.
The following list is an example of the relationship between datapoint names and
descriptors:
Datapoint Name Descriptor
Room temp floor 1 Heating circuit, West wing
Room temp floor 3 Heating circuit, West wing
Room temp floor 10 Heating circuit, East
Room temp corridor Heating circuit, East
Flow temp floor 1 Heating circuit, West wing
Lights floor 1 Building section V
Lights corridor Building section V
Descriptor
See "Description" section.