FALCON USER GUIDE
EN2Z-0962GE51 R0715 54
Direction
Datapoint Type AI AO AV BI BO BV MI MO
MV
PC RI RO
HTML Interface CARE
Editing - X
Lon Point
Shows whether a mapped datapoint is mapped to an input NV (NV in) or an output
NV (NV out).
See also "Lon Point" section.
Engineering Unit
AI AO AV BI BO BV MI MO
MV
PC RI RO
User Interface HTML Interface CARE
"assigned to value" X
Engineering units are pre-defined by the BACnet standard and will be assigned to
datapoints in CARE. In the Excel Web HTML Interface, the present value is
displayed with the assigned engineering unit.
Examples:
If, for instance, the external temperature is measured by an analog datapoint, the
engineering unit of this datapoint must be set to "°C" or "°F". If the electrical load is
detected by a pulse converter input, the engineering unit must be set to "kWh" for
kilowatt-hours.
In the Excel Web HTML Interface, engineering units are displayed read only.
EOV / EOV Optimization
AI AO AV BI BO
BV MI MO
MV
PC RI RO
User Interface HTML Interface CARE
x X
Equivalent
Defines whether the datapoint should be optimized or not, if the datapoint is used as
setpoint for energy optimized heating or ventilation (EOH or EOV).
Event
AI AO AV BI BO
BV MI MO
MV
PC RI RO
HTML Interface CARE
Editing "see Reporting" X
Reporting
Shows the transition types that can be selected for reporting:
− To Off-Normal
The alarm reaches off-normal state, that is, the datapoint value exceeds
the high limit, or remains under the low limit.