USER GUIDE FALCON
59 EN2Z-0962GE51 R0715
IO Configuration
Datapoint Type
AI
AO
AV
BI
BO
BV
MI
MO
MV
PC
RI
RO
User Interface HTML Interface CARE
Editing
x
Equivalent
The I/O configuration is not visible in the Excel Web HTML Interface, but only in
CARE.
Analog input and output points must be configured prior to their assignment to a
particular terminal on a module in CARE. This is done by selecting the appropriate
configuration such as NTC, PT100 Type F, etc., for the datapoint. The assignment
of the configuration results in the automatic setting of the configuration properties for
the datapoint.
For pull-up resistor handling, please refer to the "Pull-Up Resistor Handling" section.
Is Alarm Condition
Datapoint Type
AI AO AV BI BO
BV MI MO
MV
PC RI RO
User Interface HTML Interface CARE
Editing
x x
Equivalent In Alarm
Defines the state which enables the ´Alarm` flag. If enabled, the alarm text of the
corresponding transition event is displayed.
Example:
State Text Is Alarm Condition Alarm Text Display
1 NO NO
2 YES YES
See also "In Alarm" section.
Is Fault Condition
Datapoint Type AI AO AV BI BO
BV MI MO
MV
PC RI RO
User Interface
HTML Interface CARE
Editing x x
Equivalent
Fault
Defines the state which enables the ´Fault` flag. If enabled, the fault text of the
corresponding transition event is displayed.
Example:
State Text
Is Fault Condition
Alarm Text Display
1 NO NO
2
YES
YES
See also "Fault" section.