FALCON USER GUIDE
EN2Z-0962GE51 R0715 188
Enter alarm delay in s into the Alarm Delay field.
State Text, Is Alarm Condition, Is Fault Condition (applies to MI and MV
datapoint type only)
For Multi-State Inputs and Multi-State Value datapoints you can define the
states which represent and set off an ´Off-Normal` and/or a ´Fault` event.
Each state can be set for setting off an ´To-Off-Normal` and/or a ´Fault` event.
For each state, check the conditions by clicking the corresponding radio button.
2. Click the SUBMIT button to save settings.
3. To view /edit datapoint values, click on the Values tab (see "View / Edit Values"
section.
View / Edit Values
Procedure 1. In the Details dialog box of the selected datapoint, select the Values tab.