USER GUIDE FALCON
63 EN2Z-0962GE51 R0715
Editing
x
Equivalent
Generates and indicates the ´out of service` status of the datapoint. The ´out of
service` property allows decoupling the physical input or output from the datapoint.
For inputs the decoupling is done by manual override. For outputs this is done by
checking the ´Out of Service` flag.
The ´out of service` property is suited to fix the physical input or output state, e.g. in
case of maintenance checks.
In the following, the states of the ´out of service` flag/property of the various BACnet
objects are listed:
AI, BI, MI
Out Of Service = unchecked:
Present value has not been overwritten
Out Of Service = checked:
Present value has been overwritten
Present value is decoupled from the physical input and will not track changes to the
physical input.
AO, BO, MO
Out Of Service = checked:
Changes to the present value are decoupled from the physical output.
The present value property is still controlled by the prioritization mechanism (Priority
Array, Relinquish Default)
AV, BV, MV
Out Of Service = checked:
Present value is prevented from being modified by the application.
The present value property is still controlled by the prioritization mechanism (Priority
Array, Relinquish Default)
Pulse Converter
Out Of Service = unchecked:
Present value has not been overwritten
Out Of Service = checked:
Present value has been overwritten
Present value is decoupled from the Count property and will not track changes to
the input.
See also "In Alarm" and "Fault" sections.
Output NV
Datapoint Type
AI AO AV BI BO
BV MI MO
MV
PC RI RO
User Interface HTML Interface CARE
Editing
- x
Equivalent NV Type
Defines the network variable type (NVT) of the Lon point in CARE, e.g.
SNVT_lev_percent for an analog output point (NV - Output).
See also "Input NV" section.
Period
Datapoint Type AI AO AV BI BO
BV MI MO
MV
PC RI RO
User Interface
HTML Interface CARE