USER GUIDE FALCON
183 EN2Z-0962GE51 R0715
NOTE: Only those datapoints can be displayed of which read access level is
equal to or lower than the read access level of the user.
Datapoints can have the following properties:
Name
A datapoint´s details can be edited by clicking on its name
Value/Unit
Shows the current value with engineering unit (analog datapoint) or state
(digital datapoint)
Event State
Shows the transition type
Normal
The alarm is going to normal state, that is, the value of the datapoint remains
under the high limit, or exceeds the low limit.
Off-Normal
The alarm reaches off-normal state, that the datapoint value exceeds the
high limit, or remains under the low limit.
Fault
The alarm originates in a fault such as sensor break, etc.
High Limit
Point value has exceeded the high limit. Special case of the Off-Normal state
of analog inputs, analog outputs, and analog values.
Low Limit
Point value has dropped below the low limit. Special case of the Off-Normal
state of analog inputs, analog outputs, and analog values.
Type
e.g. AI, AO, etc.
ALM = point is in alarm
FLT = point has a fault
OVR = point value is overridden
OOS = point is out of service
4. To view or edit details of a datapoint, click on the datapoint name.
NOTE: Only those datapoints are displayed and can be edited of which read
access level is equal to or lower than the read access level of the user.
5. To sort the list, click the BROWSE button at the Sort by field.
View / Edit Datapoint Details
Viewing/editing datapoint details may include the following:
View general properties such description, point role, LON mapping data, and
access rights
Manually override the present value, that switch between Manual and Auto mode
Enable/disable alarm reporting
View alarm status (flags)
Change COV value
Change Relinquish Default value
Enable/disable Off-Normal conditions
View/edit event enrollment alarming
Continue with the "General Procedure" which describes where the functions will be
accessible.