USER GUIDE FALCON
51 EN2Z-0962GE51 R0715
Change of Value Increment
See "Increment" section.
Bit Mask
Datapoint Type
AI
AO
AV
BI
BO
BV
MI
MO
MV
PC
RI
RO
User Interface HTML Interface CARE
Editing
-
X
Equivalent Event Parameters
The bitmask shows the values/conditions that are observed.
See also "Bit String(s)" and "Event Enrollment"sections.
Bit String(s)
Datapoint Type
AI AO AV BI BO BV MI MO
MV PC RI RO
User Interface HTML Interface CARE
Editing
- X
Equivalent List of Values
Bit String(s) shows the possible logical values (true, false) resulting from the
comparison of the selected values/conditions and the underlying bitstring mask.
See also "Bit Mask" and "Event Enrollment"sections.
Characteristic
Datapoint Type AI AO AV BI BO BV MI MO
MV PC RI RO
User Interface HTML Interface CARE
Editing X
Equivalent
If the datapoint should be mapped to a NV (see LON Mapping property) and the
engineering units of both do not match, for example, the NV has °C and the
datapoint has °F, a characteristic (conversion table) must be assigned.
Default characteristics are delivered with the CARE software.
Examples: 2-10 V = 0-100 %
Linear input
Direct out 0-100 %
+1
-1
etc.
For example, the characteristic “Linear input” converts volts (NV value) into percent
(datapoint value) as follows:
NV value DP value
0,000 0,000
10,000 100,00
COV Period
See "Period" section.