Datapoint Type
AI AO AV BI BO BV MI MO
MV PC RI RO
User Interface HTML Interface CARE
Editing
x X
Equivalent
The alarm delay determines how long a ´To-Off-Normal` or a ´To-Normal` transition
must exist before an alarm is generated. Entering an alarm delay time of 10 seconds
means that the limit value must be exceeded for at least 10 seconds before this
datapoint generates an alarm. If the limit value only lasts for 7 seconds, then no
alarm occurs. The alarm handling for a datapoint can be completely disabled by
setting the alarm delay time to a value of 100000 or higher.
Alarm Text
Datapoint Type
AI AO AV BI BO BV MI MO
MV PC RI RO
User Interface HTML Interface CARE
Editing
- X
Equivalent
For the property ´Alarm text`, CARE allows entering personalized alarm texts for the
different event states of an analog or digital point. The assigned alarm text is shown
with the alarm, which is caused by the corresponding transition event.
Alarm texts can have 256 characters at maximum with no restriction on the used
character type.
Analog points have twelve, Digital points have six possible event states. The
following table shows the event states and examples for alarm texts:
Nr. Analog Event States Alarm Text Example Digital Event States Alarm Text Example
1 High Limit to Normal Value below High Limit Fault to Normal Input OK
2 Low Limit to Normal Value above Low Limit Normal to Fault Input Failure
3 Fault to Normal Sensor OK Off-Normal to Normal Input back to Normal
4 Normal to High Limit Value above High Limit Normal to Off-Normal Input Change to Alarm
5 Normal to Low Limit Value below Low Limit Fault to Off-Normal
6 Low Limit to High Limit Off-Normal to Fault
7 High Limit to Low Limit
8 Fault to High Limit
9 Fault to Low Limit
10 Normal to Fault Sensor Break
11 High Limit to Fault Sensor Break
12 Low Limit to Fault Sensor Break
Alarm Type
Datapoint Type
AI AO AV BI BO BV MI MO
MV PC RI RO
User Interface
HTML Interface CARE
Editing - X
Equivalent
Notify Type
According to the BACnet Specification, events can be of the type ´alarm` or ´event`.
On the EBI, alarms will be graphically indicated by blinking in the status line and
shown in the alarm summary. Events will not be indicated in the status line and will
be shown in the event summary.