FALCON USER GUIDE
EN2Z-0962GE51 R0715 62
These default notification classes match the default notification classes of the EBI
central.
Each recipient assigned to a notification class will receive the datapoint alarm
triggered by the selected notification. But, alarms will only be generated for the
enabled transitions (To-Normal, To-OffNormal, and/or To-Fault) of a recipient. Each
enabled transition will be propagated with the selected notification (see also “Alarm
and Event Priority Classification” section).
This connection has not to be mixed up with the transitions selected under
Transition Events (see "Transition Events" section).
Notify Type
AI AO AV BI BO
BV MI MO
MV
PC RI RO
User Interface HTML Interface CARE
- x
Equivalent Alarm Type
The notify type can be defined and changed in CARE. In the Excel Web HTML
Interface, the notify type (alarm type) is displayed only.
For all notification classes, the notify type ´Alarm` must be used.
According to the BACnet Specification, events can be of the type ´alarm` or ´event`.
On the EBI, alarms will be graphically indicated by blinking in the status line and
shown in the alarm summary. Events will not be indicated in the status line and will
be shown in the event summary.
See also "Alarm Type" section.
NV Name
AI AO AV BI BO
BV MI MO
MV
PC RI RO
User Interface HTML Interface CARE
- x
Equivalent
Shows the name of the NV, e.g. NViInsideAirTemp , that is mapped to the
datapoint.
NV Type
Datapoint Type AI AO AV BI BO
BV MI MO
MV
PC RI RO
Editing - x
Input NV, Output NV
Shows the type of the mapped NV, e.g. SNVT_temp.
See also "Input NV" and "Output NV" sections.
Out Of Service
Datapoint Type AI AO AV BI BO
BV MI MO
MV
PC RI RO
HTML Interface CARE