USER GUIDE FALCON
61 EN2Z-0962GE51 R0715
With Excel Web it is possible to disable both High and Low Limit alarms at the same
time, if the alarm delay time is set to 100,000 sec or longer.
Manual
Datapoint Type
AI
AO
AV
BI
BO
BV
MI
MO
MV
PC
RI
RO
User Interface HTML Interface CARE
Editing
x
Equivalent
Sets the datapoint in manual operation mode in which the present value will be
overwritten with a desired value manually entered by the user.
See also "Active Text / Inactive Text" section.
Manual Life Safety
Datapoint Type
AI AO AV BI BO
BV MI MO
MV
PC RI RO
User Interface HTML Interface CARE
Editing
x
Equivalent
Shows the status of the manual override switch or potentiometer of the LON
module.
Mapping
Datapoint Type AI AO AV BI BO
BV MI MO
MV
PC RI RO
User Interface
HTML Interface CARE
Editing -
Equivalent
Shows the mapping type of a mapped datapoint. For example, if the datapoint is
mapped to the present value property, PV = Present Value is displayed.
Notification Class
Datapoint Type AI AO AV BI BO
BV MI MO
MV
PC RI RO
User Interface
HTML Interface CARE
Editing - x
Equivalent
The notification class can be defined and changed in CARE. In the Excel Web
HTML Interface, only the name of the notification class is displayed.
The notification class enables alarming for the datapoint by selecting a notification
class with a given priority. By default, the following notification classes with
descending priority can be selected:
- Urgent
- High
- Low