USER GUIDE FALCON
233 EN2Z-0962GE51 R0715
General
Displays alarm details, such as event type, alarm reason and alarm text.
Event Type
Different datapoints may cause different event types as shown in the
following:
Change of state
Present value has changed to a new state for longer than the time delay.
Can be caused by BI, BO, BV, MI, MO, MV.
Out of range
Present value has exceeded range between high limit and low limit for
longer than the time delay.
Or, present value has returned between the high limit - deadband and the
low limit + deadband range for longer than the time delay.
Can be caused by AI, AO, AV.
Command failure
Present value differs from feedback value for longer than the time delay.
Can be caused by AO, BO, MO.
Acknowledged
(Not required)
NOTE:
Alarm acknowledgement is not applicable, hence alarms are set to NO
by default.
Category
Shows the category:
Urgent
Alarm has urgent priority (range 0…84)
High
Alarm has high priority (range 85…169)
Low
Alarm has low priority (range 170…250)