43-TV-25-30 Iss.6 GLO Aug 07 UK 273
Glbv GLBVx Get the global variable x. This is a global varia-
ble accessible to all scripts. There is a maxi-
mum of 200 global variables.
HPC1 to HPC48 HPC1 High Pulse count using Pulse cards
Internal memory hours left INTHRS Returns the amount of hours left until the inter-
nal memory starts to recycle (over-write).
IOC1 to IOC48 IOC1 Digital Input/Output counters for Digital in and
relay out
LPC1 to LPC48 LPC1 Low Pulse count using Digital IO cards in pulse
count mode
Pen Pn Get the value of Pen n (1 to 96)
Pen Minimum Value PnMINU Gets the Pen Minimum value n = 1 to 96
Pen Maximum Value PnMAXU Gets the Pen Maximum value n = 1 to 96
Pen report Maximum Value prmax[x,y,z] Gets the Pen Maximum value for a report. x =
pen number (1 to 96). y = period (1 = hour, 2 =
day, 3 = week, 4 = month). z = report set (1 =
current, 2 = previous completed)
Pen report Minimum Value prmin[x,y,z] Gets the Pen Minimum value for a report. x =
pen number (1 to 96). y = period (1 = hour, 2 =
day, 3 = week, 4 = month). z = report set (1 =
current, 2 = previous completed)
Pen report Average Value prave[x,y,z] Gets the Pen Average value for a report. x =
pen number (1 to 96). y = period (1 = hour, 2 =
day, 3 = week, 4 = month). z = report set (1 =
current, 2 = previous completed)
Pen report Totaliser Value prtot[x,y,z] Gets the Pen Totaliser value for a report. x =
pen number (1 to 96). y = period (1 = hour, 2 =
day, 3 = week, 4 = month). z = report set (1 =
current, 2 = previous completed)
Power Relay PWRREL Returns the status of the fixed power relay
Pstv PSTVx Get the persisted Global variable x. Persisted
global variables maintain their value through a
power cycle. There is a maximum of 50 per-
sisted global variables.
PRC PRC Power Relay Counter
Pulse Inputs (AI slots) HPULn Get the Pulse frequency from the Pulse card n
= 1 to 48 (25kHz max)
Pulse Inputs (DIO Slots) LPULn Get the Pulse frequency from the Digital Input
card when in Pulse mode n = 1 to 48 (1kHz
Max)
RT Compensation RTCOMPn Get RT Compensation value for channel n (1 to
48) Units mV
Table 14.1 : Maths Variable Table
Maths Variables Syntax Description

Table of Contents

Other manuals for Honeywell Minitrend QX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Minitrend QX and is the answer not in the manual?

Honeywell Minitrend QX Specifications

General IconGeneral
BrandHoneywell
ModelMinitrend QX
CategoryVoice Recorder
LanguageEnglish

Related product manuals