300 43-TV-25-30 Iss.6 GLO Aug 07 UK
Low Eng - (only available when Dual point is selected). Set the Low limit for the Engineer-
ing units.
Low Offset - enter an offset value that is offset against the Low Eng value.
High Eng - (only available when Dual point is selected). Set the High limit for the Engineer-
ing units.
High Offset - enter an offset value that is offset against the High Eng value.
-10V
+10V
-10V
+10V
Single Point Sensor Compensation is
used to offset the signal input by a user
specified amount over the full range.
Dual Point Sensor Compensation is used to
offset the signal input by a user specified
amount against the Low and High Eng val-
ues. The offset amount can vary throughout
the signal input range.
Solid line shows without compensation
and dotted line shows with compensation
Low Offset of 5
High Offset of -5
Figure App H.21 Sensor Compensation
100 High Eng
0 Low Eng