8.8 Series 3 PLC Network Interface and Options
The Vertex M can also communicate via the local HMI, a remote HMI, via OPC tags, and via
relays as described in "Relay Output Contacts" on page185. Additionally, the data can be
provided to a variety of fieldbuses via optional gateways. All of this is sketched in Figure 8.28.
Figure 8.28
The Vertex M presents status as an array of 244 byte as described in Table 8-10 . The values of
these data are defined in tables 8-8 and 8-9. Optional gateways translate this data into a
variety of fieldbus protocols as listed in Table 8.11. Connecting external networks directly to the
internal PLC is not supported. The Fieldbus interfaces are read-only. Write operations are either
rejected or ignored.
Protocol Name Honeywell Part Number Section
Profibus - DP 1290-0102 See "Profibus - DP" on page239
Profinet 1290-0105 See "Profinet" on page239
Modbus/TCP 1290-0106 See "Modbus/TCP" on page239
Ethernet/IP 1290-0107 See "Ethernet/IP" on page240
DeviceNet 1290-0104 See "DeviceNet" on page241
ControlNet 1290-0103 See "ControlNet" on page243
Table 8.11
Vertex M 229 User Manual