Figure 8.41
5. Select Online/Connect
6. Select Online/Upload
Note: The original configuration files are stored in the DAq in C:/hmi/Fieldbusses/gateway
configurations.
7. Select the lower network as highlighted in blue in Figure 8.42
Figure 8.42
8. Adjust the Input I/O data Size as highlighted in green in Figure 8.42. Since monitoring the
fault bytes and heartbeat is essential, the minimum usable size is 82 bytes.
9. Select Online/Download Configuration.
10. Verify the message box Finished! is displayed. This normally happens in about 30 seconds.
11. Disconnect the USB cable.
Vertex M 237 User Manual