Wiring Details
The terminals accept 0.5…1.5 mm² (22…16 AWG) solid or stranded copper wire.
The positive output terminals of the 5069-OF8 are listed in table 8-20, below. Terminals 1 to 15
are the common negative. Terminals 16 and 17 are grounds for the shields. Additional shield
terminations are available on the lower DIN rail as highlighted in green. The maximum loop
resistance is 500 Ω .
Channel mapping is defined by the following Table 8-20.
Vertex M Point Analog Output Card Output Positive Terminal Number
1-1-1
Card 1
0
1-1-2 2
1-1-3 4
1-1-4 6
1-1-5 8
1-1-6 10
1-1-7 12
1-1-8 14
1-2-1
Card 2
0
1-2-2 2
1-2-3 4
1-2-4 6
1-2-5 8
1-2-6 10
1-2-7 12
1-2-8 14
1-3-1
Card 3
0
1-3-2 2
1-3-3 4
1-3-4 6
1-3-5 8
1-3-6 10
1-3-7 12
1-3-8 14