Figure 5-1.
Figure 5-2 is an image of the Point Detail section of the main Vertex M display screen
snapshot.
Analyzer The analyzer type
Points / Alarms A point may be enabled but the alarm may be disabled
Gas Data
Name of the gas or gases, up to three gases per location
Current concentration for each gas
Alarms, if any, for that point and gas. This field shows “on” or blank.
Point Color Legend This legend defines the background colors in the system display area
Note: A Vertex M system equipped with two or more analyzer modules can monitor up to three
different gases per location. However, an analyzer may not be programmed for more than one
gas family at a time. When the Vertex M system is configured for multiple gases per location,
touching a point on the system display area will also change the border on other points
monitoring the same location. The information for a location displayed in the point detail area
will be identical regardless of which point is selected in the system display area.