Message
associated with.. meaning.. ..possible action
Program not running
at card x
Any Card Problem with software, the watchdog will operate the
MCC / MCB (main control card/board).
Software errors will activate an automatic
system reset.
Ignore for single occurrence.
Record event in the log book.
Program runaway at
card x
Any Card CPU has crashed. Clear and ignore single occurrence. Record in
the log book.
Q buffer full at
card x
Any Card Software error. Software errors will activate a system reset.
Ignore single occurrence. Record the event in
the log book.
Q buffer number
Failed at card x
Any Card Software error. Software errors will activate a system reset.
Ignore single occurrence. Record the event in
the log book.
Radio devices
recovered
LRT Radio LRT has completed finding all of the radio
devices
-
Recover failed at
card x
LPC
(loop processor card)
Loop does not match with what is in NVM. Check and confirm/correct the difference and
then backup.
Recover succeeded at
card x
LPC
(loop processor card)
Successful recovery after a previous failure. -
Replaced Device Wrong
type number x on
loop y
LPC
(loop processor card)
Device is a different type. Check and confirm installation of correct type
and reallocate. Back up to memory.
SAFE Address not Set
up number x on loop y
LPC
(loop processor card)
The replaced device is not SAFE addressed. The
device previously installed in the location was SAFE
addressed.
Set up the SAFE address.
Scan error number x
at card y
LPC
(loop processor card)
Invalid universal scan reply. Check loop length and screening