Message
associated with.. meaning.. ..possible action
System Printer fitted
at card x number y
loop z
MCC / MCB
(main control card/board)
A 80 column serial printer is fitted to the panel. -
System Printer Lost
at card x number y on
loop z
MCC / MCB (Printer option) TBA TBA
System Restarted
/Started
MCC / MCB
(main control card/board)
Link on back plane restored. -
System stopped MCC / MCB
(main control card/board)
Backplane link moved causing the system to stop. The link should not be normally accessed.
Task stuck at card x Any Card Software error. Software errors will activate a system reset.
Ignore single occurrence. Record the event in
the log book.
Test set found /
removed at card x
LPC
(loop processor card)
Remote allocation unit has been found connected to the
system.
Disconnection of the test set will bring about a
removed message.
Too many errors
number x on loop y
Device More than 15 errors from a device in 34 hours. Check the loop wiring to the device.
Too many errors x at
Card y
Network Card Up to 6 consecutive communication errors. Check wiring and cable screen. There may be
faults with the installation.
Two controller at
card x
Network There are two network controllers. One network controller will automatically shut
down.
Two master has the
same address at
card x
MCC / MCB / DAC Two PCs have been given the same address. Each PC must have a unique address.
Unable to claim
buffers at
card x
Any Card System too busy Wait or reset card if stuck, record in the log
book
Unrecoverable Tx
fault number x loop y
LPC
(loop processor card)
More than 3 consecutive reply errors Check the device connections and replace if
necessary.
Commissioning instructions
136 4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.
Appendix B - Message Action List