NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
4 Commissioning
Issue 01 (2017-07-27)
110
Parameter
Description
Configuration Principle
Default
Value
function is enabled, this
device works in harmony
with others that in the same
group.
Teamwork
mode
Set the teamwork mode. The
options include Smart only.
/
Smart
Network
Networking mode for the
teamwork. The networking
mode set on the screen must
be consistent with the actual
networking mode.
Otherwise, the teamwork
control function will be
unavailable. If the
networking mode changes,
select the corresponding
networking mode on the
screen. If the networking
mode is changed on the
screen, the software will
restart and then run in the
new networking mode.
Networked over CAN or
MAC_CAN. CAN
indicates teamwork control
over a CAN bus,
MAC_CAN teamwork
control over an FE port.
MAC_CAN
Total
number of
units
Number of the precision air
conditioners in this group (1
to 32 can be set).
Total number of the
precision air conditioners
in this group.
3
Number of
running
units
Number of active units in a
group. The value ranges from
1 to Total number of units.
The master unit assigns the
devices to be active units
by the device number,
beginning with the address
1 until to 32. The rest will
become the standby ones.
2
Rotation
Disable or enable the active
and standby precision air
conditioners to change
identity after a certain time,
maximizing their service life.
This function is
recommended when the
heat is even.
Disable
Rotation
period
Rotation days (130).
7 by default
7 day(s)
Rotation
time
24 hours in a day (023).
0 by default
0
Forced
rotation
Forced rotation specifies
whether to enable a forcible
rotation on the group before
the specified rotation time.
After a forced rotation, the
accumulated time is
This item is set to "No" by
default. If forced rotation is
required, the function is set
to "Yes".
No