NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
function is enabled, this
device works in harmony
with others that in the same
group.
Set the teamwork mode. The
options include Smart only.
Networking mode for the
teamwork. The networking
mode set on the screen must
be consistent with the actual
networking mode.
Otherwise, the teamwork
control function will be
unavailable. If the
networking mode changes,
select the corresponding
networking mode on the
screen. If the networking
mode is changed on the
screen, the software will
restart and then run in the
new networking mode.
Networked over CAN or
MAC_CAN. CAN
indicates teamwork control
over a CAN bus,
MAC_CAN teamwork
control over an FE port.
Number of the precision air
conditioners in this group (1
to 32 can be set).
Total number of the
precision air conditioners
in this group.
Number of active units in a
group. The value ranges from
1 to Total number of units.
The master unit assigns the
devices to be active units
by the device number,
beginning with the address
1 until to 32. The rest will
become the standby ones.
Disable or enable the active
and standby precision air
conditioners to change
identity after a certain time,
maximizing their service life.
This function is
recommended when the
heat is even.
24 hours in a day (0–23).
Forced rotation specifies
whether to enable a forcible
rotation on the group before
the specified rotation time.
After a forced rotation, the
accumulated time is
This item is set to "No" by
default. If forced rotation is
required, the function is set
to "Yes".