NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
4 Commissioning
Issue 01 (2017-07-27)
109
Figure 4-24 Teamwork settings
Step 2 Set teamwork control parameters.
All teamwork control parameters can be set on the master air conditioner. Only Teamwork
group no., Teamwork unit address, Teamwork CAN resistor enable, Teamwork function
and Network can be set on slave air conditioners. Table 4-10 describes how to set the
parameters.
Table 4-10 Teamwork settings
Parameter
Description
Configuration Principle
Default
Value
Teamwork
group no.
The number of the teamwork
controlled group, which is
the same for all the devices
in the group.
Set the assigned teamwork
control number.
1
Teamwork
unit address
Only one device in each
group can be set to 1. Other
device addresses should be
different from each other.
Set the assigned unit
address.
NA
Teamwork
CAN
resistor
enable
Indicates the build-out
resistor status of each
precision air conditioner in a
teamwork group.
Set this parameter to No
for non-teamwork
scenarios.
For teamwork
scenarios, set this
parameter to Yes for the
first and last precision
air conditioners in a
teamwork group, and
set it to No for other
precision air
conditioners.
No
Teamwork
function
Disable or enable the
teamwork function. If the
teamwork function is
disabled, this device is
operating according to its
own control. If the teamwork
Set this parameter based on
the onsite device heat
distribution.
Disable