NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
5 Operation and Maintenance
Issue 01 (2017-07-27)
140
Alarm
ID
Alarm
Alarm
Severity
Impact
Possible Cause
Solution
PSU 2
fault
generated.
a054
PSU 1
comm
interrupt
PSU 2
comm
interrupt
Major
The alarm
is
generated.
1. The communication
cables of the PSU are
faulty.
2. The PSU is faulty.
3. The communication port
of the control board is
faulty.
1. Check the
communication cables of
the PSU.
2. Maintain or replace the
PSU.
3. Maintain or replace the
control board.
a055
Discharge
temp
sensor
fault
Major
The alarm
is
generated.
1. Cables to the exhaust air
temperature sensor are
not properly connected.
2. The discharge
temperature sensor is
faulty.
1. Check cables to the
exhaust air temperature
sensor.
2. Maintain or replace the
exhaust air temperature
sensor.
a056
Discharge
pressure
sensor
fault
Major
The alarm
is
generated.
1. The cables to the press
sensor are loose or
damaged.
2. The press sensor is faulty.
1. Check the cables to the
press sensor.
2. Replace the press sensor.
a057
Comp
discharge
HP
Major
The alarm
is
generated,
and the
compresso
r shuts
down.
1. The outdoor unit input
power has an open phase,
incorrect phase sequence,
or is unavailable.
2. Signal cables to the
outdoor unit are not
properly connected.
3. The condenser fins are
blocked.
4. The outdoor fan driver or
fan is faulty.
5. The press displayed is
different from the actual
press.
6. The refrigerant is
overfilled.
1. Check the power supply
of the outdoor unit.
2. Check the signal cables to
outdoor unit.
3. Clean the condenser fins.
4. Maintain or replace the
outdoor unit or unit
driver.
5. Calibrate or replace the
press sensor.
6. Decrease certain amount
of refrigerant.
a058
Comp
discharge
HP lock
Critical
The alarm
is
generated,
and the
compresso
r shuts
down.
The a057 comp discharge
HP alarm is generated
frequently.
Reference to the solutions
for the a057 comp discharge
HP alarm.
a059
Suction
pres
sensor
fault
Major
The alarm
is
generated.
1. The cables to the press
sensor are loose or
damaged.
2. The press sensor is faulty.
1. Check the cables to the
press sensor.
2. Maintain or replace the
press sensor.