The alarm
is
generated,
and the
compresso
r shuts
down.
1. The refrigerant leaks.
2. The cables to the press
sensor are loose or
damaged.
3. The pressure sensor
displayed is different
from the actual pressure.
4. The filter dryer is
blocked.
5. The expansion valve is
blocked.
6. The indoor fans are
faulty.
7. The ambient temp is low.
1. Identify and repair the
leaking point, and refill
refrigerant after
maintenance.
2. Check the cables to the
press sensor.
3. Calibrate or replace the
pressure sensors.
4. Maintain or replace the
filter dryer.
5. Maintain or replace the
expansion valve.
6. Maintain or replace the
indoor fans.
7. Check the ambient temp.
The alarm
is
generated,
and the
compresso
r is locked
and not
allowed to
be started.
The a060 comp LP alarm is
generated frequently.
Refer to the solutions for the
a060 comp LP alarm.
The alarm
is
generated,
and the
compresso
r shuts
down.
1. The comp driver is faulty.
2. The comp is faulty.
1. Maintain or replace the
comp driver.
2. Maintain or replace the
comp.
The alarm
is
generated,
and the
compresso
r shuts
down.
1. The cables to the comp
driver are loose or
damaged.
2. The comp driver is faulty.
1. Check the cables to the
comp driver.
2. Maintain or replace the
comp driver.
The alarm
is
generated,
and the
compresso
r shuts
down.
1. The comp driver is faulty.
2. The comp is faulty.
1. Maintain or replace the
comp driver.
2. Maintain or replace the
comp.
1. The power supply voltage
is high.
1. Check the power supply
voltage.