NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
C Parameter Description
Issue 01 (2017-07-27)
252
Menu
Parameter
Description
Default Value
ports 1 and 2 for reporting common alarms
are open and generate no alarms.
Outdoor fan
control mode
Select the control mode for the outdoor fan
based on the cable connection of the indoor
and outdoor units (dry contact cable or RS485
cable).
Communicate
Cooling
The cooling function can be set to Enable or
Enabled when active pwr
Enable
Settings >
System
Settings >
System Control
Units start time
integral
Specifies the time interval between the starts
of units under teamwork control.
2s
Disallow on/off
via EMS
When the function is disallowed, the EMS is
not allowed to turn on or off the devices.
No
Silent mode
When the silent mode is enabled, the indoor
unit is running in low noise mode. When the
silent mode is disabled, the indoor unit is
running in normal mode.
Enable
Cooling
The cooling function can be set to Enable or
Enabled when active pwr
Enable
Heat
Enable indicates that the electric heater will
be started when the ambient temperature is
lower than the certain temperature range of
the temperature set point. Disable indicates
that the electric heater will not be started.
Enabled when active pwr indicates that the
electric heater will be started when the main
power is active and the ambient temperature
is lower than the certain temperature range of
the temperature set point.
Enable
Heat mode
If Dehumid heat is selected, the electric
heater starts heating based on the current
temperature only after the dehumidification
function is enabled. If Low-temp heat is
selected, the electric heater starts heating
based only on the current temperature, no
matter the dehumidification function is
enabled or not. If Dehumid & LT heat is
selected, the electric heater starts heating
when the dehumidification and heating
condition or the low temperature heating
condition is met.
Dehumid heat
Humid
Enable indicates that the electric humidifier
will be started when the ambient humidity is
lower than the certain humidity range of the
humidity set point. Disable indicates that the
electric humidifier will not be started.
Enabled when active pwr indicates that the
electric humidifier will be started when the
Enable