NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
C Parameter Description
Issue 01 (2017-07-27)
251
Menu
Parameter
Description
Default Value
power is active and the ambient temperature
is lower than the certain temperature range of
the temperature set point.
Heat mode
If Dehumid heat is selected, the electric
heater starts heating based on the current
temperature only after the dehumidification
function is enabled. If Low-temp heat is
selected, the electric heater starts heating
based only on the current temperature, no
matter the dehumidification function is
enabled or not. If Dehumid & LT heat is
selected, the electric heater starts heating
when the dehumidification and heating
condition or the low temperature heating
condition is met.
Dehumid heat
Humid
Enable indicates that the electric humidifier
will be started when the ambient humidity is
lower than the certain humidity range of the
humidity set point. Disable indicates that the
electric humidifier will not be started.
Enabled when active pwr indicates that the
electric humidifier will be started when the
main power is active and the ambient
humidity is lower than the certain humidity
range of the humidity set point.
Enable
Dehumid
Enable indicates that the dehumidification
function will be enabled when the ambient
humidity exceeds the certain humidity range
of the humidity set point. Disable indicates
that the dehumidification function will not be
enabled. Enabled when active pwr indicates
that the dehumidification function will be
enabled when the main power is active and
the ambient humidity exceeds the certain
humidity range of the humidity set point.
Enable
DO associated
alarm
When DO associated alarm is set to
Smoke&water only, if a smoke sensor
alarm or water overflow alarm is
generated, port 1 for reporting common
alarms generates a dry contact close alarm,
and port 2 for reporting common alarms
does not function.
When DO associated alarm is set to
Critical&major ALM, if a critical alarm
is generated, port 1 for reporting common
alarms generates a dry contact close
alarm; if a major alarm is generated, port 2
for reporting common alarms generates a
dry contact close alarm.
When DO associated alarm is set to None,
Smoke&water only