NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
It is recommended that you retain the default
value 16100. If you need to change the value,
enter a value as required. This parameter is
configurable when Link mode is set to
Client.
Settings >
Comm
Settings >
SNMP Settings
See 4.5.7 Setting Communications Parameters (SNMP Parameters).
Settings >
Alarm Settings
Three options are available for setting
whether to report an alarm.
Enable: Alarms are reported to the EMS.
The LCD displays active alarms and the
system implements related protection
actions.
Disable: Alarms are not reported and no
protection actions are implemented.
Specifies the delay time for reporting alarms.
Specifies the alarm threshold for a certain
alarm.
Settings >
System
Settings >
COMM Settings
Cold-aisle, Hot-aisle, Return-air, or
Supply-air can be set as required. The
temperature and humidity set points
correspond to the selected control type can be
set.
Ctrl temp setpoint
at ctrl point
After the T/H control type and the
temperature value under this type are set, the
device conducts cooling or heating based on
the settings.
Ctrl humid
setpoint at ctrl
point
After the T/H control type and the humidity
value under this type are set, the device
conducts humidifying or dehumidifying based
on the settings.
The sensors in cold aisles can be set to
Enable or Disable.
The sensors in hot aisles can be set to Enable
or Disable.
Enable indicates that the electric heater will
be started when the ambient temperature is
lower than the certain temperature range of
the temperature set point. Disable indicates
that the electric heater will not be started.
Enabled when active pwr indicates that the
electric heater will be started when the main