● The equipment room must be far away from residential areas. An equipment
room that is not far away from residential areas must comply with equipment
room construction standards to avoid noise pollution.
● The room should be located far away from industrial and heating boilers.
● The room should be at least 3.7 km (2.30 mi.) away from the seaside or salt
lake. Otherwise, the equipment room should be airtight with cooling facilities.
In addition, alkalized soil cannot be used as the construction material.
Otherwise, equipment suitable for wet conditions must be used.
● The doors and windows of the equipment room must be kept closed to
maintain an airtight room.
● Using steel doors to ensure sound insulation is recommended.
● No cracks or openings are allowed on the walls or
oors. The outlet holes on
the walls or windows must be sealed. Walls must be constructed such that
they are smooth, wear-resistant, dustproof,
ame retardant, sound insulated,
heat absorptive, and have electromagnetic shielding.
● The air vent of the room should be far from the exhaust of city waste pipes,
big cesspools and sewage treatment tanks. The room should be in the positive
pressure state to prevent corrosive gases from entering the equipment room
and corroding components and circuit boards.
● It is recommended that the room be on or above the second
oor. If this
requirement cannot be met, the ground for equipment installation in the
room should be at least 600 mm (23.62 in, ) above the maximum ood level.
● The equipment room should be strong enough to resist winds and downpours.
● The room should be located away from dusty roads or sand. If this is
unavoidable, the doors and windows of the equipment room must not face
pollution sources.
● Do not place air conditioning vents near the equipment so that they blow
directly on the equipment because condensation may be blown into the
equipment.
● Do not use decorative materials that contain sulfur in the equipment room.
Equipment Room Layout
An equipment room usually contains mobile switching equipment,
telecommunications equipment, power supply equipment, and other auxiliary
equipment. To ensure easy maintenance and management, place the equipment
in
dierent rooms. Figure 4-284 shows the layout of the equipment room.