SD1 Series Inverters Fault Tracking
-108-
Fault
code
Fault type Possible cause Solutions
OC1
Over-current
during
acceleration
Acceleration is too fast.
Grid voltage is too low.
Inverter power is too small.
Load transients or is
abnormal.
To-ground short circuit or
output phase loss occur.
There is strong external
interference.
The overvoltage stall
protection is not open.
Increase acceleration time.
Check input power.
Select the inverter with a
larger power.
Check if the load is short
circuited (to-ground short
circuit or line-to-line short
circuit) or the rotation is not
smooth.
Check the output wiring.
Check if there is strong
interference.
Check the setting of
related function codes.
OC2
Over-current
during
deceleration
OC3
Over-current
when running
at constant
speed
OV1
Over-voltage
during
acceleration
The input voltage is
abnormal.
There is large energy
feedback.
No brake components.
Braking energy is not
open.
Check the input power.
Check if the load
deceleration time is too
short or the inverter starts
during the rotation of the
motor, or it is necessary to
install dynamic braking
components.
Install the brake
components.
Check the setting of
related function codes.
OV2
Over-voltage
during
deceleration
OV3
Over-voltage
when running
at constant
speed
UV
DC bus
under-voltage
The voltage of the power
supply is too low.
Check the input power of
the supply line.
OL1 Motor overload
The voltage of the power
supply is too low.
The motor setting rated
current is incorrect.
The motor stall or load
transients are too strong.
Check grid voltage.
Reset the rated current of
the motor.
Check the load and adjust
the torque lift.