SD1 Series Inverters Fault Tracking
-109-
Fault type Possible cause Solutions
OL2
Inverter
overload
Acceleration is too fast.
Restart the rotating motor
Grid voltage is too low.
The load is too heavy.
The rated power is much
larger than the power
Increase acceleration time.
Avoid restarting after
stopping.
Check the grid voltage.
Select an inverter with
larger power.
OL3
Electrical
overload
overload pre-alarm
according to the set value.
Check the load and the
overload pre-alarm point.
SPI
Input phase
Phase loss or fluctuation of
Check input power
Check installation wiring.
SPO
Output phase
loss
U, V, W phase loss output
(or serious asymmetrical
three phase of the load).
Check the motor and
OH1
Rectify
overheat
Air duct is blocked, or fan
is damaged.
Ambient temperature is too
high.
The time of overload
running is too long.
Refer to the overcurrent
solution.
Redistribute.
Clear the wind channel or
change the fan.
Decrease the ambient
temperature.
Check and reconnect.
Change the power.
Change the power unit.
Change the main control
OH2 IGBT overheat
EF External fault
SI external fault input
terminals acts.
Check the external device
input.
CE
Communication
error
The baud rate setting is
incorrect.
Fault occurs to the
communication circuit.
The communication
address is wrong.
There is strong
interference to the
Set proper baud rate.
Check the wiring of
communication connection
interface.
Set proper communication
address.
Change or replace the
wiring or improve the
anti-interference capability.