SD1 Series Inverters Function Parameters
-60-
Function
code
Name Description Default Modify
BIT5: S6 virtual terminal
BIT6: S7 virtual terminal
BIT7: S8 virtual terminal
BIT8: HDI virtual terminal
Note: After a virtual terminal is enabled, the state
of the terminal can only be modified through
communication, and the communication address
is 0x200A.
P05.13
Terminal
control running
mode
Set the operation mode of the terminals control
0: 2-wire control 1; Combine
the enable with the
direction. This mode is widely used. It
determines the rotation direction by the defined
FWD and REV terminals command.
FWD
REV
COM
K1
K2
Running
command
FWD REV
OFF OFF
OFF
OFF
ON
ON
ON ON
Stopping
Hold on
Forward
running
Reverse
running
1: 2-wire control 2;
Separate the enable from the
direction. FWD defined by this mode is the
enabling ones. The direction depends on the
state of the defined REV.
FWD
REV
COM
K1
K2
Running
command
FWD REV
OFF OFF
OFF
OFF
ON
ON
ON ON
Stopping
Stopping
Forward
running
Reverse
running
2: 3-wire control 1; Sin is the enabling terminal in
this mode, and the running command is caused
by FWD, and the direction is controlled by REV.
Sin is natural closed.
0